VS1-12(ZN63A) Indoor Side loading VCB
Detailed Product Description
- Working Condition
Altitude:1000m and below;
Environmental temperature is from:-15~40°C;
Environmental humidity:
Daily average of relative humidity≤95%
Daily average saturated vapor pressure≤2.2×10-3Mpa
Monthly average of relative humidity≤90%
Monthly average saturated vapor pressure≤1.8×10-3Mp
No operating in such environment as subject to dust, dirt, smog, corrosive/flammable gas, vapor and salt pollution.
Earthquake intensity: No more than 8 degree - Technical Data
Rated voltage: 10kV (highest voltage 12kV)
Rated current: 630A, 1250A, 1600A.
Rated short circuit breaking current: 20kA, 25kA, 31.5kA.
One minute power frequency withstand voltage (kV): 42 (phase ground), 48 (fracture)
Lighting impact withstand voltage (kV): 75 (phase ground ), 85 (fracture)
4s rated short-time withstand current (effective value): 20kA, 25kA, 31.5kA.
Rated peak value withstand current (peak value): 50kA, 63kA, 80kA.
Rated short circuit making current (peak value): 50kA, 63kA, 80kA.
Rated individual capacitor bank breaking current: 630A
Rated back-to-back capacitor bank breaking current: 400A