Wankong Group Co., Ltd.

home products Vacuum circuit breaker VW1-12 Mid-voltage solid encapsulated vacuum circuit breaker

VW1-12 Mid-voltage solid encapsulated vacuum circuit breaker

Product Details:

Type Vacuum
Poles Number 3
Place of Origin Zhejiang, China (Mainland)
Brand Name WANKONG
Model Number VW1-12

Payment & Shipping Terms:

Minimum Order Quantity: 1 Piece/Pieces
Packaging Details: Wooden
Delivery Time: Within 20days
Payment Terms: L/C,T/T
Supply Ability: 150 Piece/Pieces per Day

Detailed Product Description


1. General
    The VW1-12 series adopt the latest and mature technology of automatic Pressure Gelation (APG) to embed the vacuum interrupter and connection terminals within resin. The vacuum interrupter is casted in the resin, which makes the circuit-breaker poles particularly sturdy and reliability and protects the interrupter against shocks, accumulation of dust and humidity. Thanks to the embedded pole design, the distribution of electrical field of the pole is much even than in the assembly pole vacuum circuit-breaker, so the insulation strength of VW1 series MV embedded pole vacuum circuit-breaker is improved dramatically.
 

2. Working Condition
    Guarantee the ambient environment temperature within -15~+40, the daily average temperature not exceed +35;
    Daily average related humidity not exceed 95%, monthly not exceed 90%;
    The altitude not exceed 3000m above the sea level;
    Earthquake intensity is not more than 8 degree horizontal acceleration.
    The ambient air without contamination of erosion and combustible gas, vapor, etc.

 

3. Technical Data

Code

Item

Unit

Data

1

Rated voltage

kV

12

2

rated frequency

Hz

50

3

Rated lighting impact withstand voltage(peak value)

kV

75

4

power frequency withstand voltage (1 min)

kV

42

5

Rated current

A

     630     630   1250
    1250    1250  1600

6

Rated short-circuit breaking current

kV

       20     25      31.5 

7

Rated short-time withstand current (virtual value)

kV

      20      25      31.5

8

Rated peak withstand current (peak value)

kV

    50      63      80 

9

Rated short-circuit making current (peak value)

kV

  50      63      80

10

Duration of rated short-circuit current

s

4

11

Rated operating order

O-0.3-CO-180s-CO  O-180s-CO-180s-CO

12

Rated breaking current of single/symmetrical capacitor bank

A

630/400 (40kA:800/400)

13

Rated making surge current of capacitor bank

kV

20 (frequency:4250Hz)

14

Contact clearance

mm

11±1

15

Contact travel

mm

3.5±0.5

16

Bounce time of contact making

ms

≤2

17

Out of simultaneity of three-phase making and breaking

ms

≤2

18

Average breaking speed

m/s

0.9~1.2

19

Average making speed

m/s

0.5~0.8

20

Breaking time (rated voltage)

ms

20~50

21

Making time (rated voltage)

ms

35~70

22

Rated operation voltage of making and breaking

V

AC110/220, DC110/220

23

Rated voltage of energy storage motor

V

AC110/220, DC110/220

24

Rated Power of energy storage motor

W

70,100 (40kA)

25

Energy storage time

s

≤15

26

Permitted abrasion thickness of moving and fixed contacts

mm

≤3

27

Rebound amplitude of contact breaking

mm

≤2

28

Main circuit resistance

         630A      ≤50µΩ
        1250A     ≤45µΩ
   1600-2000A  ≤35µΩ

VW1-12 Mid-voltage solid  encapsulated vacuum circuit breaker VW1-12 Mid-voltage solid encapsulated vacuum circuit breaker

Send your message to this supplier
« Prev Product 1 2 3 4 5 6 Next Product »